Line Fail
Sent when the UPD goes on-battery, repeated every 30 seconds until
low-battery condition reached. Sometimes occurs more than once in the
first 30 seconds.
Return from Line Fail
	
UPS back on line power, only sent if a Line Fail has been sent.
Low Battery
	
Sent to indicate low battery, but not on SmartUPS v/s or BackUPS Pro models.
Return from Low Battery
	
Sent when the battery has been recharged to some level, only if a Low
	Battery has been sent previously.
Abnormal Condition
Sent for conditions such as "shutdown due to overload" or "shutdown
	due to low battery capacity".
	Also occurs within 10 minutes of
	Turn On.
Return from Abnormal
	Sent when the UPS returns from an abnormal condition where Abnormal
	Condition was sent, but not a
	Turn On. Not implemented on SmartUPS
	v/s or BackUPS Pro models.
About to Turn Off
	Sent when the UPS is about to switch off the load. No commands are
	processed after this character is
	sent. Not implemented on SmartUPS
	v/s, BackUPS Pro, or third generation
	SmartUPS models.
Replace Battery
	
Sent when the UPS detects that the battery needs to be replaced. Sent
	every five hours until a new battery
	test is run or the UPS is shut off.
	Not implemented on SmartUPS v/s or
	BackUPS Pro models.
Check Alarm Register for Fault (Measure-UPS)
	Sent to signal that temperature or humidity is out of set limits. Also sent when one of the contact closures changes states. 
Sent every two minutes, stops
	when the alarm conditions are reset.
	Only sent for alarms enabled with I.
	Cause of alarm may be determined by
	asking the UPS. Not implemented
	on SmartUPS v/s or BackUPS Pro.
Variable Change
	Sent whenever any EEPROM variable is changed. Only supported in EEPROM on Matrix UPS
	and third generation SmartUPS models.