Line Fail
Sent when the UPD goes on-battery, repeated every 30 seconds until
low-battery condition reached. Sometimes occurs more than once in the
first 30 seconds.
Return from Line Fail
UPS back on line power, only sent if a Line Fail has been sent.
Low Battery
Sent to indicate low battery, but not on SmartUPS v/s or BackUPS Pro models.
Return from Low Battery
Sent when the battery has been recharged to some level, only if a Low
Battery has been sent previously.
Abnormal Condition
Sent for conditions such as "shutdown due to overload" or "shutdown
due to low battery capacity".
Also occurs within 10 minutes of
Turn On.
Return from Abnormal
Sent when the UPS returns from an abnormal condition where Abnormal
Condition was sent, but not a
Turn On. Not implemented on SmartUPS
v/s or BackUPS Pro models.
About to Turn Off
Sent when the UPS is about to switch off the load. No commands are
processed after this character is
sent. Not implemented on SmartUPS
v/s, BackUPS Pro, or third generation
SmartUPS models.
Replace Battery
Sent when the UPS detects that the battery needs to be replaced. Sent
every five hours until a new battery
test is run or the UPS is shut off.
Not implemented on SmartUPS v/s or
BackUPS Pro models.
Check Alarm Register for Fault (Measure-UPS)
Sent to signal that temperature or humidity is out of set limits. Also sent when one of the contact closures changes states.
Sent every two minutes, stops
when the alarm conditions are reset.
Only sent for alarms enabled with I.
Cause of alarm may be determined by
asking the UPS. Not implemented
on SmartUPS v/s or BackUPS Pro.
Variable Change
Sent whenever any EEPROM variable is changed. Only supported in EEPROM on Matrix UPS
and third generation SmartUPS models.